Grundfos TPE 100-140/4 A3-F-Y-DQQE-LWA (99114263)

Product ID: 99114263

Request Price and Availability

Grundfos TPE 100-140/4 A3-F-Y-DQQE-LWA (99114263)
Part Number: 99114263

Grundfos TPE 100-140/4 A3-F-Y-DQQE-LWA (99114263)

Controls:
Frequency converter:Built-in
Liquid:
Pumped liquid:Water
Liquid temperature range:-40 .. 140 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:1483 rpm
Rated flow:97.76 m³/h
Rated head:13.39 m
Actual impeller diameter:214 mm
Primary shaft seal:DQQE
Code for shaft seal:DQQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Ductile iron
 EN-GJS-400-18-LT
 ASTM Grade 60-40-18
Impeller:Bronze
 CuSn10-C
Installation:
Range of ambient temperature:-20 .. 50 °C
Maximum operating pressure:25 bar
Max pressure at stated temp:25 bar / 140 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 100
Pressure rating for connection:PN 25
Port-to-port length:670 mm
Flange size for motor:FF265
Electrical data:
Motor type:132SG
Rated power - P2:5.5 kW
Mains frequency:50 Hz
Rated voltage:3 x 380-500 V
Rated current:10.5-8.40 A
Cos phi - power factor:0.92-0.88
Rated speed:180-2200 rpm
IE Efficiency class:IE5
Motor efficiency at full load:91.9 %
Number of poles:4
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:93108491
Others:
Minimum efficiency index, MEI ≥:0.45
Net weight:207 kg
Gross weight:236 kg
Shipping volume:0.743 m³

Spare Parts

Part NumberProduct Name
98164277Spare, Plug vent

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.