Grundfos TPE 100-530/2 NC-A3-F-O-DQQE-TW1 (92843523)

Product ID: 92843523

Request Price and Availability

Grundfos TPE 100-530/2 NC-A3-F-O-DQQE-TW1 (92843523)
Part Number: 92843523

Grundfos TPE 100-530/2 NC-A3-F-O-DQQE-TW1 (92843523)

Controls:
VFD product number:99616825
Frequency converter:Built-in
Type of frequency converter:CUE 3X380-500V IP55 RUG 45KW
Appr. for VFD:CE, CULUS, C-TICK
Liquid:
Pumped liquid:Water
Liquid temperature range:-40 .. 140 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:2983 rpm
Rated flow:201.9 m³/h
Rated head:54.07 m
Actual impeller diameter:215 mm
Primary shaft seal:DQQE
Code for shaft seal:DQQE
Curve tolerance:ISO9906:2012 3B
Materials:
Pump housing:Ductile iron
 EN-GJS-400-18-LT
 ASTM Grade 60-40-18
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-10 .. 50 °C
Maximum operating pressure:25 bar
Max pressure at stated temp:25 bar / 140 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 100
Pressure rating for connection:PN 25
Port-to-port length:670 mm
Flange size for motor:FF400
Electrical data:
Motor type:225M
Rated power - P2:45 kW
Mains frequency:50 Hz
Rated voltage:3 x 400 V
Rated current:84 A
Cos phi - power factor:0.96
Rated speed:300-3000 rpm
IE Efficiency class:IE5
Motor efficiency at full load:96.2 %
Number of poles:2
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:92669180
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:385 kg
Gross weight:496 kg
Shipping volume:2.07 m³

Spare Parts

Part NumberProduct Name
98164277Spare, Plug vent
99208810Spare, Wear ring

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.