Grundfos TPD 40-530/2 A-F-B-BQQE-MW1 (98743251)

Product ID: 98743251

Request Price and Availability

Grundfos TPD 40-530/2 A-F-B-BQQE-MW1 (98743251)
Part Number: 98743251

Grundfos TPD 40-530/2 A-F-B-BQQE-MW1 (98743251)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-25 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:2961 rpm
Rated flow:30.13 m³/h
Rated head:42.17 m
Actual impeller diameter:200 mm
Primary shaft seal:BQQE
Code for shaft seal:BQQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Bronze
 CuSn10-C
Installation:
Range of ambient temperature:-30 .. 60 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 40
Pressure rating for connection:PN 16
Port-to-port length:440 mm
Flange size for motor:FF265
Electrical data:
Motor type:132SB
Rated power - P2:7.5 kW
Mains frequency:50 Hz
Rated voltage:3 x 380-415D/660-690Y V
Rated current:14,4-14,0/8,30-8,10 A
Starting current:780-910 %
Cos phi - power factor:0.88-0.86
Rated speed:2910-2920 rpm
IE Efficiency class:IE3
Motor efficiency at full load:90.1-90.4 %
Motor efficiency at 3/4 load:90.8-90.9 %
Motor efficiency at 1/2 load:90.8-90.4 %
Number of poles:2
Enclosure class (IEC 34-5):55 Dust/Jetting
Insulation class (IEC 85):F
Motor No:87370232
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:202 kg
Gross weight:225 kg
Shipping volume:0.683 m³

Spare Parts

Part NumberProduct Name
98164277Spare, Plug vent

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.