Grundfos TPD 65-720/2 A-F-A-BQQE-QW1 (93426625)

Product ID: 93426625

Request Price and Availability

Grundfos TPD 65-720/2 A-F-A-BQQE-QW1 (93426625)
Part Number: 93426625

Grundfos TPD 65-720/2 A-F-A-BQQE-QW1 (93426625)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-25 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:2945 rpm
Rated flow:69.8 m³/h
Rated head:59.9 m
Actual impeller diameter:230 mm
Primary shaft seal:BQQE
Code for shaft seal:BQQE
Curve tolerance:ISO9906:2012 3B
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 65
Pressure rating for connection:PN 16
Port-to-port length:475 mm
Flange size for motor:FF300
Electrical data:
Motor type:WEG
Rated power - P2:22 kW
Mains frequency:50 Hz
Rated voltage:3 x 380-415D/660Y V
Rated current:40,9-39,2/23,5 A
Starting current:920-1090 %
Cos phi - power factor:0.87
Rated speed:2960 rpm
IE efficiency:IE4 94%
IE Efficiency class:IE4
Motor efficiency at full load:94 %
Motor efficiency at 3/4 load:93.5-93.3 %
Motor efficiency at 1/2 load:92.6-92 %
Number of poles:2
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:93123945
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:453 kg
Gross weight:488 kg
Shipping volume:1.14 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.