Grundfos TP 100-800/2 A3-F-O-DQQE-VW1 (99087073)

Product ID: 99087073

Request Price and Availability

Grundfos TP 100-800/2 A3-F-O-DQQE-VW1 (99087073)
Part Number: 99087073

Grundfos TP 100-800/2 A3-F-O-DQQE-VW1 (99087073)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-40 .. 140 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:2978 rpm
Rated flow:251 m³/h
Rated head:72.61 m
Actual impeller diameter:245 mm
Primary shaft seal:DQQE
Code for shaft seal:DQQE
Curve tolerance:ISO9906:2012 3B
Materials:
Pump housing:Ductile iron
 EN-GJS-400-18-LT
 ASTM Grade 60-40-18
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:25 bar
Max pressure at stated temp:25 bar / 140 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 100
Pressure rating for connection:PN 25
Port-to-port length:670 mm
Flange size for motor:FF500
Electrical data:
Motor type:INNOMOTICS
Rated power - P2:75 kW
Mains frequency:50 Hz
Rated voltage:3 x 380-420D/660-725Y V
Rated current:126/73 A
Starting current:850 %
Cos phi - power factor:0.9
Rated speed:2978 rpm
IE efficiency:IE4 95,6%
IE Efficiency class:IE4
Motor efficiency at full load:95.6 %
Motor efficiency at 3/4 load:95.8 %
Motor efficiency at 1/2 load:95.6 %
Number of poles:2
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:92898766
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:756 kg
Gross weight:807 kg
Shipping volume:2.14 m³

Spare Parts

Part NumberProduct Name
98164277Spare, Plug vent

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.