Grundfos TP 65-210/2 A-F-A-BQQE-JW1 (98858611)

Product ID: 98858611

Request Price and Availability

Grundfos TP 65-210/2 A-F-A-BQQE-JW1 (98858611)
Part Number: 98858611
Checking availability
BUY NOW

Grundfos TP 65-210/2 A-F-A-BQQE-JW1 (98858611)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-25 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:2909 rpm
Rated flow:46.3 m³/h
Rated head:16.8 m
Actual impeller diameter:127 mm
Primary shaft seal:BQQE
Code for shaft seal:BQQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 65
Pressure rating for connection:PN 16
Port-to-port length:360 mm
Flange size for motor:FF215
Electrical data:
Motor type:INNOMOTICS
Rated power - P2:3 kW
Mains frequency:50 Hz
Rated voltage:3 x 380-420D/660-725Y V
Rated current:5.70/3.3 A
Starting current:900 %
Cos phi - power factor:0.86
Rated speed:2920 rpm
IE efficiency:IE4 89,1%
IE Efficiency class:IE4
Motor efficiency at full load:89.1 %
Motor efficiency at 3/4 load:89.8 %
Motor efficiency at 1/2 load:89.4 %
Number of poles:2
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:83U16210
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:63.8 kg
Gross weight:82 kg
Shipping volume:0.39 m³

Spare Parts

Part NumberProduct Name
98164277Spare, Plug vent

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.