Grundfos TP 80-150/4 A-F-A-BAQE-JW3 (98858341)
Product ID: 98858341
Request Price and Availability
Grundfos TP 80-150/4 A-F-A-BAQE-JW3 (98858341)
Grundfos TP 80-150/4 A-F-A-BAQE-JW3 (98858341)
| Controls: | |
| Frequency converter: | None |
| Liquid: | |
| Pumped liquid: | Water |
| Liquid temperature range: | 0 .. 120 °C |
| Selected liquid temperature: | 20 °C |
| Density: | 998.2 kg/m³ |
| Technical: | |
| Pump speed on which pump data are based: | 1473 rpm |
| Rated flow: | 59.14 m³/h |
| Rated head: | 12.5 m |
| Actual impeller diameter: | 203 mm |
| Primary shaft seal: | BAQE |
| Code for shaft seal: | BAQE |
| Curve tolerance: | ISO9906:2012 3B2 |
| Materials: | |
| Pump housing: | Cast iron |
| EN-GJL-250 | |
| ASTM class 35 | |
| Impeller: | Cast iron |
| EN-GJL-200 | |
| ASTM class 30 | |
| Installation: | |
| Range of ambient temperature: | -20 .. 55 °C |
| Maximum operating pressure: | 16 bar |
| Max pressure at stated temp: | 16 bar / 120 °C |
| Pipe connection standard: | EN 1092-2 |
| Type of connection: | DIN |
| Size of connection: | DN 80 |
| Pressure rating for connection: | PN 16 |
| Port-to-port length: | 500 mm |
| Flange size for motor: | FF215 |
| Electrical data: | |
| Motor type: | INNOMOTICS |
| Rated power - P2: | 3 kW |
| Mains frequency: | 50 Hz |
| Rated voltage: | 3 x 380-420D/660-725Y V |
| Rated current: | 5.9/3.45 A |
| Starting current: | 880 % |
| Cos phi - power factor: | 0.81 |
| Rated speed: | 1460 rpm |
| IE efficiency: | IE4 91,0% |
| IE Efficiency class: | IE4 |
| Motor efficiency at full load: | 91.0 % |
| Motor efficiency at 3/4 load: | 91.0 % |
| Motor efficiency at 1/2 load: | 90.0 % |
| Number of poles: | 4 |
| Enclosure class (IEC 34-5): | IP55 |
| Insulation class (IEC 85): | F |
| Motor No: | 83V16210 |
| Others: | |
| Minimum efficiency index, MEI ≥: | 0.70 |
| Net weight: | 88.4 kg |
| Gross weight: | 106 kg |
| Shipping volume: | 0.395 m³ |
Spare Parts
| Part Number | Product Name |
|---|---|
| 98164277 | Spare, Plug vent |
Applications
- Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.
category
- Inline single stage pumpsIn-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.