Grundfos TP 100-150/4 A-F-A-BAQE-LW4 (98536894)

Product ID: 98536894

Request Price and Availability

Grundfos TP 100-150/4 A-F-A-BAQE-LW4 (98536894)
Part Number: 98536894
Checking availability
BUY NOW

Grundfos TP 100-150/4 A-F-A-BAQE-LW4 (98536894)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:0 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:1751 rpm
Rated flow:108 m³/h
Rated head:12.7 m
Actual impeller diameter:177 mm
Primary shaft seal:BAQE
Code for shaft seal:BAQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 100
Pressure rating for connection:PN 16
Port-to-port length:550 mm
Flange size for motor:FF265
Electrical data:
Motor type:INNOMOTICS
Rated power - P2:5.5 kW
Mains frequency:60 Hz
Rated voltage:3 x 440-480Y V
Rated current:9.3 A
Starting current:1000 %
Cos phi - power factor:0.81
Rated speed:1775 rpm
IE efficiency:IE3 91,7%
IE Efficiency class:IE3 / NEMA Premium
Motor efficiency at full load:91.7 %
Motor efficiency at 3/4 load:91.6 %
Motor efficiency at 1/2 load:90.5 %
Number of poles:4
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:83V05217
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:146 kg
Gross weight:171 kg
Shipping volume:0.56 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.