Grundfos TP 100-290/4 A-F-A-BQQE-OW4 (96111083)

Product ID: 96111083

Request Price and Availability

Grundfos TP 100-290/4 A-F-A-BQQE-OW4 (96111083)
Part Number: 96111083

Grundfos TP 100-290/4 A-F-A-BQQE-OW4 (96111083)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-25 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:1764 rpm
Rated flow:151 m³/h
Rated head:25.3 m
Actual impeller diameter:248 mm
Primary shaft seal:BQQE
Code for shaft seal:BQQE
Curve tolerance:ISO9906:2012 3B
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 100
Pressure rating for connection:PN 16
Port-to-port length:670 mm
Flange size for motor:FF300
Electrical data:
Motor type:INNOMOTICS
Rated power - P2:15 kW
Mains frequency:60 Hz
Rated voltage:3 x 400/690 V
Rated current:28.5/16.7 A
Starting current:890 %
Cos phi - power factor:0.81
Rated speed:1775 rpm
IE efficiency:IE3 93,6%
IE Efficiency class:IE3 / NEMA Premium
Motor efficiency at full load:93.6 %
Motor efficiency at 3/4 load:93.7 %
Motor efficiency at 1/2 load:93.1 %
Number of poles:4
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:92871557
Others:
Minimum efficiency index, MEI ≥:0.59
Net weight:263 kg
Gross weight:295 kg
Shipping volume:0.937 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.