Grundfos TP 50-250/2 A-F-A-BAQE-IW2 (96088845)

Product ID: 96088845

Request Price and Availability

Grundfos TP 50-250/2 A-F-A-BAQE-IW2 (96088845)
Part Number: 96088845
Checking availability
BUY NOW

Grundfos TP 50-250/2 A-F-A-BAQE-IW2 (96088845)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:0 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:3520 rpm
Rated flow:24.8 m³/h
Rated head:19.7 m
Actual impeller diameter:113 mm
Primary shaft seal:BAQE
Code for shaft seal:BAQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-30 .. 60 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 50
Pressure rating for connection:PN 16
Port-to-port length:340 mm
Flange size for motor:FF165
Electrical data:
Motor type:90LE
Rated power - P2:2.2 kW
Mains frequency:60 Hz
Rated voltage:3 x 230-277D/400-480Y V
Rated current:7,50-6,95/4,30-4,00 A
Starting current:820-1050 %
Rated speed:3480-3530 rpm
IE Efficiency class:NEMA Premium / IE3 60Hz
Motor efficiency at full load:86.5 %
Motor efficiency at 3/4 load:89.5-88.5 %
Motor efficiency at 1/2 load:89.2-86.3 %
Number of poles:2
Enclosure class (IEC 34-5):55 Dust/Jetting
Insulation class (IEC 85):F
Motor No:99583819
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:53 kg
Gross weight:65 kg
Shipping volume:0.217 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.