Grundfos TP 100-120/2 AI-F-Z-BQQE-IW1 (93470387)
Product ID: 93470387
Request Price and Availability
Grundfos TP 100-120/2 AI-F-Z-BQQE-IW1 (93470387)
Grundfos TP 100-120/2 AI-F-Z-BQQE-IW1 (93470387)
| Controls: | |
| Frequency converter: | None |
| Liquid: | |
| Pumped liquid: | Water |
| Liquid temperature range: | -25 .. 120 °C |
| Selected liquid temperature: | 20 °C |
| Density: | 998.2 kg/m³ |
| Technical: | |
| Pump speed on which pump data are based: | 2920 rpm |
| Rated flow: | 72.8 m³/h |
| Rated head: | 7.8 m |
| Actual impeller diameter: | 104 mm |
| Primary shaft seal: | BQQE |
| Code for shaft seal: | BQQE |
| Curve tolerance: | ISO9906:2012 3B2 |
| Materials: | |
| Pump housing: | Bronze |
| CuSn10 | |
| ASTM B505 | |
| Impeller: | Stainless steel |
| EN 1.4301 | |
| AISI 304 | |
| Installation: | |
| Range of ambient temperature: | -30 .. 60 °C |
| Maximum operating pressure: | 6 bar |
| Max pressure at stated temp: | 6 bar / 120 °C |
| Pipe connection standard: | EN 1092-3 |
| Type of connection: | DIN |
| Size of connection: | DN 100 |
| Pressure rating for connection: | PN 6 |
| Port-to-port length: | 450 mm |
| Flange size for motor: | FT115 |
| Electrical data: | |
| Motor type: | 90LG |
| Rated power - P2: | 2.2 kW |
| Mains frequency: | 50 Hz |
| Rated voltage: | 3 x 380-400D/660-690Y V |
| Rated current: | 4.55/2.60 A |
| Starting current: | 970-1020 % |
| Cos phi - power factor: | 0.85-0.82 |
| Rated speed: | 2920-2930 rpm |
| IE Efficiency class: | IE4 |
| Motor efficiency at full load: | 88.0 % |
| Motor efficiency at 3/4 load: | 89.7-90.0 % |
| Motor efficiency at 1/2 load: | 89.4-89.1 % |
| Number of poles: | 2 |
| Enclosure class (IEC 34-5): | 55 Dust/Jetting |
| Insulation class (IEC 85): | F |
| Motor No: | 93072821 |
| Others: | |
| Minimum efficiency index, MEI ≥: | 0.70 |
| Net weight: | 65.9 kg |
| Gross weight: | 74.5 kg |
| Shipping volume: | 0.204 m³ |
Applications
- Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.
category
- Inline single stage pumpsIn-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.