Grundfos TP 150-130/4 A-F-A-BQQE-MW3 (93426803)

Product ID: 93426803

Request Price and Availability

Grundfos TP 150-130/4 A-F-A-BQQE-MW3 (93426803)
Part Number: 93426803

Grundfos TP 150-130/4 A-F-A-BQQE-MW3 (93426803)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-25 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:1481 rpm
Rated flow:204.5 m³/h
Rated head:9.34 m
Actual impeller diameter:196 mm
Primary shaft seal:BQQE
Code for shaft seal:BQQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 150
Pressure rating for connection:PN 16
Port-to-port length:800 mm
Flange size for motor:FF265
Electrical data:
Motor type:WEG
Rated power - P2:7.5 kW
Mains frequency:50 Hz
Rated voltage:3 x 400D/690Y V
Rated current:14.4/8.35 A
Starting current:1000 %
Cos phi - power factor:0.81
Rated speed:1470 rpm
IE efficiency:IE4 92,6%
IE Efficiency class:IE4
Motor efficiency at full load:92.6 %
Motor efficiency at 3/4 load:92 %
Motor efficiency at 1/2 load:91 %
Number of poles:4
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:93123975
Others:
Minimum efficiency index, MEI ≥:0.66
Net weight:300 kg
Gross weight:329 kg
Shipping volume:0.743 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.