Grundfos TP 150-450/4 A3-F-O-DQQE-TW3 (93425397)

Product ID: 93425397

Request Price and Availability

Grundfos TP 150-450/4 A3-F-O-DQQE-TW3 (93425397)
Part Number: 93425397

Grundfos TP 150-450/4 A3-F-O-DQQE-TW3 (93425397)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-40 .. 140 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:1487 rpm
Rated flow:291.7 m³/h
Rated head:40.78 m
Actual impeller diameter:357 mm
Primary shaft seal:DQQE
Code for shaft seal:DQQE
Curve tolerance:ISO9906:2012 3B
Materials:
Pump housing:Ductile iron
 EN-GJS-400-18-LT
 ASTM Grade 60-40-18
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:25 bar
Max pressure at stated temp:25 bar / 140 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 150
Pressure rating for connection:PN 25
Port-to-port length:1000 mm
Flange size for motor:FF400
Electrical data:
Motor type:WEG
Rated power - P2:45 kW
Mains frequency:50 Hz
Rated voltage:3 x 400D/690Y V
Rated current:84.1/48.7 A
Starting current:900 %
Cos phi - power factor:0.81
Rated speed:1490 rpm
IE efficiency:IE4 95,4%
IE Efficiency class:IE4
Motor efficiency at full load:95.4 %
Motor efficiency at 3/4 load:95 %
Motor efficiency at 1/2 load:94.2 %
Number of poles:4
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:93123982
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:769 kg
Gross weight:900 kg
Shipping volume:2.38 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.