Grundfos TP 350-780/4 A3-F-O-DQQE-YW3 (93425385)

Product ID: 93425385

Request Price and Availability

Grundfos TP 350-780/4 A3-F-O-DQQE-YW3 (93425385)
Part Number: 93425385

Grundfos TP 350-780/4 A3-F-O-DQQE-YW3 (93425385)

Controls:
Frequency converter:None
Liquid:
Pumped liquid:Water
Liquid temperature range:-40 .. 140 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:1491 rpm
Rated flow:1383 m³/h
Rated head:66.11 m
Actual impeller diameter:480 mm
Primary shaft seal:DQQE
Code for shaft seal:DQQE
Curve tolerance:ISO9906:2012 3B
Materials:
Pump housing:Ductile iron
 EN-GJS-400-18-LT
 ASTM Grade 60-40-18
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 55 °C
Maximum operating pressure:25 bar
Max pressure at stated temp:25 bar / 140 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 350
Pressure rating for connection:PN 25
Port-to-port length:1400 mm
Flange size for motor:FF600
Electrical data:
Motor type:WEG
Rated power - P2:315 kW
Mains frequency:50 Hz
Rated voltage:3 x 400D/690Y V
Rated current:547/317 A
Starting current:790 %
Cos phi - power factor:0.86
Rated speed:1490 rpm
IE efficiency:IE4 96,7%
IE Efficiency class:IE4
Motor efficiency at full load:96.7 %
Motor efficiency at 3/4 load:96.5 %
Motor efficiency at 1/2 load:96 %
Number of poles:4
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:93386445
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:2410 kg
Gross weight:2550 kg
Shipping volume:6.46 m³

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.