Grundfos TPE 32-380/2 A-F-A-BAQE-JWB (99113881)

Product ID: 99113881

Request Price and Availability

Grundfos TPE 32-380/2 A-F-A-BAQE-JWB (99113881)
Part Number: 99113881
Checking availability
BUY NOW

Grundfos TPE 32-380/2 A-F-A-BAQE-JWB (99113881)

Controls:
Frequency converter:Built-in
Liquid:
Pumped liquid:Water
Liquid temperature range:0 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:2910 rpm
Rated flow:18.9 m³/h
Rated head:31.4 m
Actual impeller diameter:169 mm
Primary shaft seal:BAQE
Code for shaft seal:BAQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Cast iron
 EN-GJL-200
 ASTM class 30
Installation:
Range of ambient temperature:-20 .. 50 °C
Maximum operating pressure:16 bar
Max pressure at stated temp:16 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 32
Pressure rating for connection:PN 16
Port-to-port length:340 mm
Flange size for motor:FF215
Electrical data:
Motor type:100LA
Rated power - P2:3 kW
Mains frequency:50 Hz
Rated voltage:3 x 380-500 V
Rated current:5.80-4.80 A
Cos phi - power factor:0.91-0.86
Rated speed:360-4000 rpm
IE Efficiency class:IE5
Motor efficiency at full load:90.7 %
Number of poles:2
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:98971186
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:53.9 kg
Gross weight:72 kg
Shipping volume:0.39 m³

Spare Parts

Part NumberProduct Name
98164277Spare, Plug vent

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.