Grundfos TPE2 50-150 N-A-F-A-BQQE-FYB (98438352)

Product ID: 98438352

Request Price and Availability

Grundfos TPE2 50-150 N-A-F-A-BQQE-FYB (98438352)
Part Number: 98438352
Checking availability
BUY NOW

Grundfos TPE2 50-150 N-A-F-A-BQQE-FYB (98438352)

Controls:
Frequency converter:Built-in
Liquid:
Pumped liquid:Water
Liquid temperature range:-25 .. 120 °C
Selected liquid temperature:20 °C
Density:998.2 kg/m³
Technical:
Pump speed on which pump data are based:3800 rpm
Rated flow:22.8 m³/h
Rated head:9.5 m
Actual impeller diameter:74 mm
Primary shaft seal:BQQE
Code for shaft seal:BQQE
Curve tolerance:ISO9906:2012 3B2
Materials:
Pump housing:Cast iron
 EN-GJL-250
 ASTM class 35
Impeller:Composite
 PES+30% GF
Installation:
Range of ambient temperature:-20 .. 50 °C
Maximum operating pressure:10 bar
Max pressure at stated temp:10 bar / 120 °C
Pipe connection standard:EN 1092-2
Type of connection:DIN
Size of connection:DN 50
Pressure rating for connection:PN 6/10
Port-to-port length:280 mm
Flange size for motor:56C
Electrical data:
Motor type:80A
Rated power - P2:0.75 kW
Mains frequency:50 / 60 Hz
Rated voltage:1 x 200-240 V
Rated current:4.7-3.9 A
Cos phi - power factor:0.99
Rated speed:360-4000 rpm
IE Efficiency class:IE5
Motor efficiency at full load:85.2 %
Number of poles:0
Enclosure class (IEC 34-5):IP55
Insulation class (IEC 85):F
Motor No:99137994
Others:
Minimum efficiency index, MEI ≥:0.70
Net weight:25.2 kg
Gross weight:32.4 kg
Shipping volume:0.104 m³
Danish VVS No.:382202150
Finnish LVI No.:4616226
Norwegian NRF no.:9043487
Country of origin:HU
Custom tariff no.:84137051

Spare Parts

Part NumberProduct Name
98660096Kit, Impeller
98660103Kit, Shaft seal BQQE

Applications

  • Commercial air conditioning — Improve user comfort and reduce life-cycle costs with intelligent pumps that integrate easily into your air-based or hydronic cooling system.

category

  • Inline single stage pumps
    In-line single-stage pumps are typically used in commercial buildings for air-conditioning and heating applications. The pumps are equipped with standard motors and mechanical shaft seals. They are close-coupled, meaning that the pump and motor are two separate units, making them less sensitive to impurities in the pumped liquid.